MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-XII. AQB-A250 / A252 conversion settings - Continued.
AQB-A250 settings (SPD or
SPD AQB-A252 equivalent settings
Cutler-Hammer/Westinghouse)
Short-time
Short-time
Continuous
Instantaneous
Instantaneous
delay pickup
delay time
current setting/
Trip element
pickup (amps)
pickup (amps)
(amps)
band
rating plug
250NM
4 (2625)
250
10X (2500)
10X (2500)
3
250NM
HI (3400)
250
15X (3750)
15X (3750)
1
NOTE:
/1 See MIL-DTL-17361/6 for complete details on available settings.
80
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business