MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-VIII. AQB-A101 / AQB-A103 conversion settings /1.
AQB-A101 settings (SPD or
Cutler-Hammer AQB-A103 equivalent settings
Cutler-Hammer/Westinghouse)
Continuous
Instantaneous Short-time
Short-time
current
Instantaneous
delay pickup
delay time
pickup
Frame size
Trip element
pickup (amps)
setting
(amps)
band
(amps)
(amps)
15 A
LO (90)
25
15
6 (150)
7 (105)
MIN
15 A
2 (115)
25
15
6 (150)
7 (105)
MIN
15 A
3 (140)
25
15
6 (150)
10 (150)
MIN
15 A
4 (165)
25
15
6 (150)
10 (150)
MIN
15 A
HI (195)
25
15
8 (200)
13 (195)
MIN
25 A
LO (150)
25
25
6 (150)
7 (175)
MIN
25 A
2( 190)
25
25
8 (200)
10 (250)
MIN
25 A
3 (235)
25
25
10 (250)
10 (250)
MIN
25 A
4 (280)
25
25
12 (300)
13 (325)
MIN
25 A
HI (325)
25
25
15 (375)
13 (325)
MIN
50 A
LO (300)
100
50
6 (600)
7 (350)
MIN
50 A
2 (380)
100
50
6 (600)
7 (350)
MIN
50 A
3 (470)
100
50
6 (600)
10 (500)
MIN
50 A
4 (560)
100
50
6 (600)
13 (650)
MIN
50 A
HI (650)
100
50
8 (800)
13 (650)
MIN
75 A
LO (450)
100
80
6 (600)
5 (400)
MIN
75 A
2 (580)
100
80
6 (600)
7 (560)
MIN
75 A
3 (710)
100
80
8 (800)
10 (800)
MIN
75 A
4 (840)
100
80
8 (800)
10 (800)
MIN
75 A
HI (975)
100
80
10 (1000)
13 (1040)
MIN
100 A
LO (600)
100
100
6 (600)
7 (700)
MIN
100 A
2 (775)
100
100
8 (800)
10 (1000)
MIN
100 A
3 (950)
100
100
10 (1000)
10 (1000)
MIN
100 A
4 (1125)
100
100
12 (1200)
13 (1300)
MIN
100 A
HI (1300)
100
100
15 (1500)
13 (1300)
MIN
NOTES: