MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-X. AQB-LF250 / LF252 conversion settings /1.
AQB-LF250 settings (SPD or
SPD AQB-LF252 equivalent settings
Cutler-Hammer/Westinghouse)
Short-time
Short-time
Continuous
Instantaneous
Instantaneous
delay pickup
delay time
current setting/
Trip element
pickup (amps)
pickup (amps)
(amps)
band
rating plug
125L
LO (650)
125
3X (750)
6X (750)
1
125L
2 (780)
125
3X (750)
6X (750)
3
125L
3 (900)
125
4X (1000)
6X (750)
3
125L
4 (1040)
125
4X (1000)
8X (1000)
3
125L
HI (1300)
125
6X (1500)
10X (1250)
1
150L
LO (650)
150
3X (750)
4X (600)
1
150L
2 (780)
150
3X (750)
6X (900)
1
150L
3 (900)
150
4X (1000)
6X (900)
1
150L
4 (1040)
150
4X (1000)
8X (1200)
1
150L
HI (1300)
150
6X (1500)
8X (1200)
2
175L
LO (650)
175
3X (750)
4X (700)
1
175L
2 (780)
175
3X (750)
6X (1050)
1
175L
3 (900)
175
4X (1000)
6X (1050)
1
175L
4 (1040)
175
4X (1000)
6X (1050)
1
175L
HI (1300)
175
6X (1500)
8X (1400)
1
225L
LO (650)
225
3X (750)
3X (675)
1
225L
2 (780)
225
3X (750)
4X (900)
1
225L
3 (900)
225
4X (1000)
4X (900)
1
225L
4 (1040)
225
4X (1000)
4X (900)
3
225L
HI (1300)
225
6X (1500)
6X (1350)
1
250L
LO (650)
250
3X (750)
3X (750)
1
250L
2 (780)
250
3X (750)
3X (750)
1
250L
3 (900)
250
4X (1000)
3X (750)
3
250L
4 (1040)
250
4X (1000)
4X (1000)
3
250L
HI (1300)
250
6X (1500)
6X (1500)
1
125LM
LO (1500)
125
6X (1500)
15X (1875)
1
125LM
2 (1770)
125
8X (2000)
15X (1875)
1
125LM
3 (2025)
125
8X (2000)
15X (1875)
3
125LM
4 (2325)
125
10X (2500)
15X (1875)
3
125LM
HI (3000)
125
15X (3750)
15X (1875)
3