MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-X. AQB-LF250 / LF252 conversion settings - Continued.
AQB-LF250 settings (SPD or
SPD AQB-LF252 equivalent settings
Cutler-Hammer/Westinghouse)
Short-time
Short-time
Continuous
Instantaneous
Instantaneous
delay pickup
delay time
current setting/
Trip element
pickup (amps)
pickup (amps)
(amps)
band
rating plug
150LM
LO (1500)
150
6X (1500)
10X (1500)
2
150LM
2 (1770)
150
8X (2000)
15X (2250)
1
150LM
3 (2025)
150
8X (2000)
15X (2250)
1
150LM
4 (2325)
150
10X (2500)
15X (2250)
3
150LM
HI (3000)
150
15X (3750)
15X (2250)
3
175LM
LO (1500)
175
6X (1500)
10X (1750)
1
175LM
2 (1770)
175
8X (2000)
10X (1750)
1
175LM
3 (2025)
175
8X (2000)
15X (2625)
1
175LM
4 (2325)
175
10X (2500)
15X (2625)
1
175LM
HI (3000)
175
15X (3750)
15X (2625)
3
225LM
LO (1500)
225
6X (1500)
8X (1800)
1
225LM
2 (1770)
225
8X (2000)
8X (1800)
1
225LM
3 (2025)
225
8X (2000)
10X (2250)
1
225LM
4 (2325)
225
10X (2500)
10X (2250)
1
225LM
HI (3000)
225
15X (3750)
15X (3375)
1
250LM
LO (1500)
250
6X (1500)
6X (1500)
2
250LM
2 (1770)
250
8X (2000)
8X (2000)
1
250LM
3 (2025)
250
8X (2000)
8X (2000)
3
250LM
4 (2325)
250
10X (2500)
10X (2500)
1
250LM
HI (3000)
250
15X (3750)
10X (2500)
3
NOTE:
/1 See MIL-DTL-17361/7 for complete details on available settings.
75
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business