MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-XIII. AQB-A250 / AQB-A253 conversion settings /1.
AQB-A250 settings (SPD or
Cutler-Hammer AQB-A253 equivalent settings /2
Cutler-Hammer/Westinghouse)
Continuous
Trip
Instantaneous
Frame
Short-time delay
Short-time delay
current setting on
time band /3
element
pickup (amps)
size
pickup (amps)
adjustable rating
plug (amps)
125N
Low (650)
250
125
6 (750)
INST
125N
2 (780)
250
125
6 (750)
INST
125N
3 (900)
250
125
8 (1000)
INST
125N
4 (1040)
250
125
10 (1250)
INST
125N
High (1300)
250
125
10 (1250)
INST
150N
Low (650)
250
150
4 (600)
INST
150N
2 (780)
250
150
6 (900)
INST
150N
3 (900)
250
150
6 (900)
INST
150N
4 (1040)
250
150
8 (1200)
INST
150N
High (1300)
250
150
10 (1500)
INST
175N
Low (650)
250
175
4 (700)
INST
175N
2 (780)
250
175
4 (700)
INST
175N
3 (900)
250
175
6 (1050)
INST
175N
4 (1040)
250
175
6 (1050)
INST
175N
High (1300)
250
175
8 (1400)
INST
225N
Low (650)
250
225
3 (675)
INST
225N
2 (780)
250
225
4 (900)
INST
225N
3 (900)
250
225
4 (900)
INST
225N
4 (1040)
NA
NA
NA
NA
225N
High (1300)
250
225
6 (1350)
INST
250N
Low (650)
250
250
3 (750)
INST
250N
2 (780)
250
250
3 (750)
INST
250N
3 (900)
250
250
4 (1000)
INST
250N
4 (1040)
NA
NA
NA
NA
250N
High (1300)
250
250
6 (1500)
INST
100NG
Low (1175)
250
100
13 (1300)
INST
100NG
2 (1400)
250
100
13 (1300)
INST
100NG
3 (1620)
NA
NA
NA
NA
100NG
4 (1880)
NA
NA
NA
NA
100NG
High (2350)
NA
NA
NA
NA
160NG
Low (1950)
250
160
13 (2080)
INST
160NG
2 (2425)
250
160
13 (2080)
INST
160NG
3 (2760)
NA
NA
NA
NA
81