MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-XIV. AQB-LF400 / LF402 conversion settings - Continued.
SPD AQB-LF400 settings
SPD AQB-LF402 equivalent settings
Continuous
Short-time
Short-time
Instantaneous
Instantaneous
Trip element
current setting/
delay pickup
delay time
pickup (amps)
pickup (amps)
rating plug
(amps)
band
350TM
2 (3725)
350
10X (4000)
10X (3500)
3
350TM
3 (4325)
350
10X (4000)
12X (4200)
3
350TM
4 (5175)
350
12X (4800)
15X (5250)
1
350TM
HI (5825)
350
15X (6000)
15X (5250)
3
400TM
LO (3190)
400
8X (3200)
8X (3200)
2
400TM
2 (3725)
400
10X (4000)
10X (4000)
1
400TM
3 (4325)
400
10X (4000)
10X (4000)
3
400TM
4 (5175)
400
12X (4800)
12X (4800)
3
400TM
HI (5825)
400
15X (6000)
15X (6000)
1
NOTE:
/1 See MIL-DTL-17361/11 for complete details on available settings.
86
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.