TABLE A-VII. AQB-A101 / A102 type "E1" and "E2" conversion settings /1 /2.
AQB-A101 settings (SPD or
SPD AQB-A102 type "E1" and "E2" equivalent settings
Cutler-Hammer/Westinghouse)
Short-time
Short-time
Instantaneous
Continuous
Instantaneous
delay pickup
delay time
Trip element
pickup (amps)
current setting
pickup (amps)
(amps)
band
15A
LO (90)
15
3X (300)
6X (90)
1
15A
2 (115)
15
3X (300)
8X (120)
1
15A
3 (140)
15
3X (100)
10X (150)
1
15A
4 (165)
15
3X (300)
10X (150)
2
15A
HI (195)
15
3X (300)
10X (150)
2
25A
LO (150)
25
3X (300)
6X (150)
1
25A
2( 190)
25
3X (300)
6X (150)
2
25A
3 (235)
25
3X (300)
8X (200)
2
25A
4 (280)
25
3X (300)
10X (250)
2
25A
HI (325)
25
3X (300)
10X (250)
3
50A
LO (300)
50
3X (300)
6X (300)
1
50A
2 (380)
50
4X (400)
6X (300)
2
50A
3 (470)
50
6X (600)
8X (400)
2
50A
4 (560)
50
6X (600)
10X (500)
2
50A
HI (650)
50
6X (600)
10X (500)
3
75A /2
LO (450)
75
6X (600)
6X (450)
1
75A /2
2 (580)
75
6X (600)
6X (450)
2
75A /2
3 (710)
75
8X (800)
10X (750)
1
75A /2
4 (840)
75
8X (800)
10X (750)
3
75A /2
HI (975)
75
10X (1000)
10X (750)
3
100A
LO (600)
100
6X (600)
6X (600)
1
100A
2 (775)
100
8X (800)
6X (600)
2
100A
3 (950)
100
10X (1000)
8X (800)
2
100A
4 (1125)
100
12X (1200)
10X (1000)
2
100A
HI (1300)
100
12X (1200)
10X (1000)
3
NOTES:
/1 See MIL-DTL-17361/4 for complete details on available settings.
/2 When replacing an AQB-A101 with a 75-amp trip element, use an AQB-A102 Type "E1" circuit breaker.