MIL-PRF-83383E
3.3.6 Electronic components. Electronic components selected shall be such that the RCCB shall meet the
performance requirements and product characteristics specified herein. The manufacturer shall establish an
evaluation program in accordance with Appendix A.
3.4 Interface and physical dimensions. The RCCB shall be of the interface, weight, and physical dimensions
specified (see 3.1). All poles of triple pole RCCB's shall be mechanically ganged together.
3.4.1 Trip-free feature. The RCCB shall be such that the circuit cannot be maintained closed when any pole is
carrying overload currents that would normally automatically trip the circuit breaker to the open position.
3.4.2 Trip indication or warning label. The RCCB shall provide positive indication of the main contact position or a
warning label shall be furnished with the RCCB (see 3.1). Electrical actuation of the indicator is not acceptable.
3.4.2.1 Remote trip indication. The RCCB shall be such that when the circuit breaker contacts open automatically
on overload, the RCCB shall cause the remote actuator to indicate the operation by moving to the "open" tripped
position.
3.4.3 Attitude. The RCCB shall trip within maximum and minimum limits of the specified trip times (see 3.1, 6.5.1
3.4.4 Controls.
3.4.4.1 Indicator/control unit (I/CU). The RCCB shall be capable of remote actuation by means of an I/CU
connected between a control terminal of the RCCB and supply ground (see 3.1). A load control switch or subsystem
relay contact may be connected in series with the I/CU. The I/CU (not furnished under this specification) shall be a
0.5 ampere, trip-free circuit breaker, with trip times and internal impedance defined in the applicable specification
sheet.
3.4.5.1 Line and load terminals (see 6.5.3). The main line and load terminals shall be as specified (see 3.1). Each
terminal shall be capable of carrying rated current and voltage per pole of the RCCB.
3.4.5.2 Control and auxiliary contact terminals (see 6.5.4). The control terminals and auxiliary contact terminals
shall meet the performance of a terminal junction system (TJS) in accordance with MIL-T-81714 to accept pin contact,
part number M39029/1-100 or -101 in accordance with MIL-C-39029/1. Auxiliary contacts shall be of a single pole,
double throw configuration. The auxiliary contacts shall be arranged in a manner to insure (regardless of actuator
position) that the normally open contacts are closed when the main contacts are closed.
3.4.6 Threaded parts. Screw threads shall be in accordance with FED-STD-H28 and as specified (see 3.1).
RCCB's shall be supplied with the specified hardware assembled in proper order.
3.4.7 Solder. Solder shall not be used primarily for obtaining mechanical strength. Electrical connections shall be
mechanically secure before and electrically continuous after soldering.
3.4.8 Voltage rating. The RCCB shall have a voltage rating per pole as specified (see 3.1).
3.4.9 Continuous current carrying capacity. The RCCB shall be capable of carrying the rated current as specified
(see 3.1).
3.5 Dielectric withstanding voltage. When tested as specified in 4.6.2, the RCCB shall show no
evidence of damage, arcing, or breakdown. The leakage current shall not exceed 0.5 milliamperes.
3.6 Insulation resistance. When tested as specified in 4.6.3, the RCCB shall have an insulation resistance of not
less than 100 megohms.