MIL-PRF-83383E
3.12 Endurance. When tested as specified in 4.6.9, the RCCB shall not fail and shall show no evidence of
mechanical damage or loosening of parts.
3.12.1 Electrical operation. In addition, the RCCB shall calibrate within the limits of 90 percent of the specified
minimum ultimate trip current and 110 percent of the specified maximum ultimate trip current (see 3.7) and shall meet
the voltage drop requirement (see 3.8).
3.13 Terminal strength. When tested as specified in 4.6.10, the RCCB shall show no evidence of short-circuiting,
breakage, loosening, bending, stripping of threads, or rotation of terminals, as applicable, and no damage to the
circuit breaker body around the terminals.
3.14 Vibration. When tested as specified in 4.6.11, the RCCB main contacts shall not trip and there shall be no
opening of the closed nor closing of the open main or auxiliary contacts in excess of 10 microseconds, nor shall there
be any evidence of mechanical or electrical damage. The RCCB shall also meet the 200 percent overload calibration
requirement (see 3.7).
3.14.1 Vibration scan. When tested as specified in 4.6.11.1 or 4.6.11.2, the RCCB main contacts shall not trip, and
there shall be no opening of the closed nor closing of the open main or auxiliary contacts in excess of 10
microseconds, nor shall there be any evidence of mechanical or electrical damage. The RCCB shall also meet the
200 percent overload calibration requirements when tested at 25°C, mounted in the y-axis upon completion of the
scan.
3.15 Moisture resistance. When tested as specified in 4.6.12, the RCCB shall show no evidence of breaking,
cracking, spalling, excessive corrosion, or loosening of terminals. The RCCB shall also meet the following
requirements when tested at 25°C:
a. 1000 percent overload calibration. The RCCB must trip within ±20 percent of the specified limits
(see 3.7).
b. 400 percent trip-free calibration. The RCCB must trip within ±20 percent of the specified limits
c. 200 percent overload calibration. The RCCB must trip within ±10 percent of the specified limits
(see 3.7).
d. Dielectric withstanding voltage (see 3.5).
3.16 Thermal shock. When tested as specified in 4.6.13, the RCCB shall show no evidence of mechanical
damage.
3.17 Shock (specified pulse). When tested as specified in 4.6.14, the RCCB main contacts shall not trip. There
shall be no closing of the open main or auxiliary contacts, nor opening of the closed main or auxiliary contacts in
excess of 10 microseconds, nor shall there be any evidence of mechanical or
electrical damage. The RCCB shall also meet the 200 percent overload calibration requirements (see 3.7).
3.18 Coordination. When tested as specified in 4.6.15, the RCCB with the higher rating shall not open, the RCCB
with the lower rating shall open, and there shall be no electrical or mechanical malfunction.
3.19 Electromagnetic interference. When tested as specified in 4.6.16, the RCCB shall meet the requirements for
Aircraft, Army, Navy, and Air Force of MIL-STD-461.
3.20 Transient susceptibility. When tested as specified in 4.6.17, the RCCB shall not electrically or mechanically
malfunction.
3.21 Explosion. When tested as specified in 4.6.18, the RCCB shall not ignite the explosive mixture outside the
RCCB.
6
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business