TABLE VII. Long-time delay pickup testing (electromechanical and electronic trip units).
Trip status
Long-time
Applied
Left pole
Center pole
Right pole
All poles /2
pickup
current (amps)
setting /1
Required
Actual
Required
Actual
Required
Actual
Required
Actual
90% of nominal
No trip
No trip
No trip
No trip
LTDPU
Min.
110% of
setting
nominal
Trip
Trip
Trip
Trip
LTDPU
90% of nominal
No trip
No trip
No trip
No trip
LTDPU
Intmd.
110% of
setting
Trip
Trip
Trip
Trip
nominal
LTDPU
90% of nominal
No trip
No trip
No trip
No trip
LTDPU
Max.
110% of
setting
Trip
Trip
Trip
Trip
nominal
LTDPU
NOTES:
/1 Minimum, intermediate (or as close to middle as possible) and maximum long-time delay pickup (LTDPU) setting available on the circuit breaker, as
specified in the applicable specification sheet.
/2 For electromechanical circuit breakers, current shall flow through all poles simultaneously with poles in series. For electronic circuit breakers, three-phase
current shall flow through all poles simultaneously (not three poles in series).