MIL-PRF-55629/11E
REQUIREMENTS
Dimensions and configuration: See figure 1 and figure 2.
Current ratings: See table I.
Voltage ratings: See table I. 240 V ac breakers are designed also for use at 120 V ac.
Tripping-time delays: See table I and table II.
Terminal and mounting hardware: See figure 1.
Terminals: See figure 1. Solderability is applicable. Solder terminals are formed by removal of
screws.
Actuator strength: 25 pounds.
Actuator operating force: 12 pounds, maximum.
Terminal strength:
Applied load: 30 pounds.
Applied torque: 10 inch-pounds.
Interrupting capacities:
2,000 amperes at 50 V dc.
2,000 amperes at 120 V ac, 60 Hz.
1,500 amperes at 120 V ac, 400 Hz.
1,000 amperes at 240 V ac, 60 and 400 Hz.
Part or Identifying Number (PIN): M55629/11- (dash number from table I).
5