MIL-DTL-17361G(SH)
APPENDIX A
TABLE A-XV. AQB-LF400 / AQB-L400 conversion settings.
SPD AQB-LF400 settings
Cutler-Hammer AQB-L400/LL400 equivalent settings /1
Short-time
Short-time delay
Trip
Instantaneous
Frame
Rating plug
delay pickup
time band /2
element
pickup (amps)
size
(amps)
350TM
MAX (5825)
LL400QS
350Q
HI (5800)
MIN
400TM
MIN (3190)
LL400QM
400Q
HI (3200)
MIN
400TM
2 (3725)
LL400QS
400Q
LO (3600)
MIN
400TM
3 (4325)
LL400QS
400Q
1 (4700)
MIN
400TM
4 (5175)
LL400QS
400Q
3 (5250)
MIN
400TM
MAX (5825)
LL400QS
400Q
HI (5800)
MIN
NOTES:
/1 See MIL-DTL-17361/9 and MIL-DTL-17361/10 for complete details on available settings.
/2 "MIN" setting approximates an instantaneous function.