MIL-DTL-17361G(SH)
TABLE V. Qualification test schedule and sequence (for inspection samples 1A, 2A, and 3A) - Continued.
Test
Inspection
Requirement
Verification
number
4.5.11
3.4.5
Inclination (includes the following tests)
7
4.5.11.1
3.4.3
Manual cycling
7A
4.5.6
3.5.19
Attachment voltage range/operating characteristics
7B
4.5.6.1
3.5.19.3
Electric operating mechanism
7C
4.5.6.1.1
3.5.19.3p
Voltage range
7C(1)
4.5.6.1.2
3.5.19.3a
Closing time
7C(2)
4.5.6.2
3.5.19.4
Undervoltage release
7D
4.5.6.2.1
3.5.19.4a
Operating voltage range
7D(1)
4.5.6.2.2
3.5.19.4a
Dropout voltage range
7D(2)
4.5.6.2.3
3.5.19.4.1
Time delay
7D(3)
4.5.6.3
3.5.19.5
Shunt trip voltage range
7E
Circuit breaker temperature rise (pre-interruption)
3.4.2
4.5.12
8
3.4.6
3.5.14.4
3.5.18.4
3.5.19.1
4.5.8
8A
Auxiliary switch rating
3.5.19.6
9
Dielectric strength (full voltage)
3.4.2
4.5.4
3.5.14.2
3.5.18.1
10
Insulation resistance (10-megohm threshold)
3.4.2
4.5.5
3.5.14.3
3.5.18.1
11
Interrupting performance
3.4.7
4.5.13
4.5.12
12
Circuit breaker temperature rise (post-interruption)
3.4.2
3.4.6
3.5.14.4
3.5.18.4
3.5.18.1
13
Dielectric strength (reduced voltage)
3.4.2
4.5.4
3.5.14.2
3.5.18.1
14
Insulation resistance (1-meghom threshold)
3.4.2
4.5.5
3.5.14.3
3.5.18.1
15
Abbreviated calibration
3.4.4
4.5.10.3
16
Handle locking device operation
3.5.19.7
4.5.18
17
Handle boot operation and high temperature endurance
3.5.19.8
4.5.19
NOTE: Refer to the applicable circuit breakers individual specification sheet (see 3.1) for additional test
information and requirements.