W-C-375E
TABLE xIII. Available current in test circuit.
Frame rating |
RMS symmetrical |
||||
1 pole |
2 pole |
3 pole |
|||
Individual |
Common |
Individual |
Common |
||
100A maximum 250 V maximum 100A maximum 251-600V 101-800A any voltage 801-1,200 any voltage 1,201-1,600 1,601-2,000 2,001-2,500 2,501-3,000 3,001-4,000 |
5,000 10,000 10,000 --- --- --- --- --- --- |
5,000 10,000 10,000 14,000 14,000 14,000 20,000 25,000 30,000 |
5,000 10,000 10,000 14,000 20,000 25,000 30,000 30,000 45,000 |
4,330 1/ 8,660 1/ 2/ 8,660 1/ 2/ 12,120 1/ 2/ 14,000 14,000 20,000 25,000 30,000 |
5,000 10,000 10,000 14,000 20,000 25,000 30,000 35,000 45,000 |
1/ This value is the current available when using two legs of the 3-phase circuit indicated under "Common".
2/ For the 277/480 volt rating, the current indicated for 2-pole under "Individual" shall be used.
TABLE xIV. Short-circuit operations.
Poles |
Frame rating |
Circuit breaker-AC voltage rating |
Operations by each pole |
Common operations |
Total number of operations |
||||
O |
CO |
O (see 6.6.2) O |
CO |
O |
|||||
1 1 2 2 2 2 3 3 3 3 3 |
All All All All 0-1200A All 0-1200A 1201-Up All 0-1200A 1201-UP |
120, 240, 277, 480, or 600 120/240 (tested in pairs) 240,480, or 600 120/240 277/480 10/30 240, 480, or 600 240, 480, or 600 120/240 277/480 277/480 |
x --- x --- x x x x --- x x |
x --- x --- x x x x --- x x |
x --- --- --- --- --- --- --- --- --- --- |
--- x x x x x x x x x x |
--- x --- x --- --- --- x x --- x |
--- x --- x --- --- --- --- x --- --- |
3 3 5 3 5 5 7 8 3 7 8 |