W-C-375/13B
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1. Electrical:
Interrupting current rating: RMS symmetrical, 10,000 amperes. Voltage rating: 120/240 V ac.
Trip current: See table I. Frequency: 60 hertz. Calibration: At +40°C.
Enclosure for overload, endurance, and short circuit tests: 15 through 30 ampere breakers, Federal
Pacific Electric Catalog No. 102-2F/S; 35 through 50 ampere breakers, Catalog No. 102-4F/S, or equivalent.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
WC375/13-001 WC375/13-002 WC375/13-003 WC375/13-004 WC375/13-005 WC375/13-006 WC375/13-007 WC375/13-008 |
15 20 25 30 35 40 45 50 |
TABLE II. Supersession and cross reference.
Government PIN |
Superseded number |
Will replace number |
|||
CAGE 21810 |
|||||
WC375/13-001 WC375/13-002 WC375/13-003 WC375/13-004 WC375/13-005 WC375/13-006 WC375/13-007 WC375/13-008 |
15 20 25 30 35 40 45 50 |
NA15 NA20 NA25 NA30 NA35 NA40 NA45 NA50 |
15H 20H 25H 30H 35H 40H 45H 50H |
NA15H NA20H NA25H NA30H NA35H NA40H NA45H NA50H |
NAH15H NAH20H NAH25H NAH30H NAH35H NAH40H NAH45H NAH50H |