TABLE V. Operating voltage, frequency, and tripping-time delay (configuration 2). 1/
Tripping-time delay at 25°C ±2°C (tripping time in seconds)
Time
50 V dc
240 V ac, 60 Hz
240 V ac, 400 Hz
delay
percent
rated
K
L
M
N
P
R
S
current
Max
Min
Max
Min
Max
Min
Max
Min
Max
Min
Max
Min
Max
Min
no trip
no trip
no trip
no trip
no trip
no trip
no trip
100
one hour
one hour
one hour
one hour
one hour
one hour
one hour
125
60
7
6.5
0.5
120
10
12
0.7
N/A
N/A
N/A
N/A
N/A
N/A
150
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
70
5
8
0.5
400
40
200
10
0.6
1.2
0.13
20
2.2
3
0.13
25
2.1
1.9
0.15
150
9.5
400
2
0.15
0.5
0.031
3
0.3
1
0.03
5
0.4
0.4
0.02
19
1.9
600
1
Inst
0.25
Inst
2
Inst
0.3
Inst
2.4
Inst
0.25
Inst
7
Inst
800
0.5
Inst
0.1
Inst
0.8
Inst
0.15
Inst
1
Inst
0.1
Inst
0.4
Inst
1,000
0.1
Inst
Inst
Inst
0.25
Inst
0.1
Inst
0.1
Inst
0.05
Inst
0.043
Inst
1,800 2/
no trip
no trip
no trip
no trip
no trip
no trip
no trip
See footnotes at end of table VI.
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business