MIL-PRF-39019F
f.
Examination after test: Examine for evidence of breaking, cracking, spalling, or loosening of terminals.
g.
Tests after moisture resistance test: Circuit breakers shall be subjected to the following tests:
(1)
Dielectric withstanding voltage (see 4.8.3).
(2)
Calibration (see 4.8.6.2).
(3)
Seal (4.8.8).
(4)
Panel seal (see 4.8.9).
MIL-STD-202. The following details shall apply.
a.
Mounting: Normal mounting means and in such a manner that there is at least 1 inch of free air space around
each circuit breaker.
b.
Test condition: B.
c.
Examination after cycling: Circuit breakers shall be examined for evidence of mechanical damage.
4.8.16 Shock (specified pulse) (see 3.19). Circuit breakers shall be tested in accordance with method 213 of
MIL-STD-202. The following details shall apply.
a.
Mounting method: Normal mounting means.
b.
Test condition: I.
c.
Electrical load conditions and measurements: Of the three shocks in each direction required, two shocks shall
be performed with the circuit breaker energized at 100 percent of rated current at 12 volts dc, except that for
the directions with the operating lever pivot up (table mount) and the operating lever pivot down (ceiling
mount), no voltage or current shall be applied. Each energized shock shall be monitored to determine opening
of the main or auxiliary circuit breaker contacts. The remaining shock in each direction shall be performed with
the circuit breaker contacts open and unenergized and shall be monitored to determine closing of the main or
auxiliary contacts.
d.
Examination after shock (see 3.19): Circuit breakers shall be examined for evidence of mechanical and
electrical damage.
4.8.17 Trip free calibration (see 3.20). The circuit breaker lever shall be physically held in the closed position and
the breaker subjected to the calibration test as specified in 4.8.6.1.
22
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business