W-C-375/70
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1.
Common trip: All poles shall make and break simultaneously when operated manually or automatically.
Electrical:
Interrupting current rating: 10,000 amperes. Voltage rating: 120/240 V ac.
Currency rating: See table I. Frequency: 60 hertz. Calibration: At +40°C, ±3°C
Enclosure for overload, endurance, and short circuit tests: Cutler Hammer catalog number CH2L125FP
or equivalent.
Supersession and cross reference: See table II.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
Figure number |
WC375/07-001 WC375/07-002 WC375/07-003 WC375/07-004 WC375/07-005 WC375/07-006 WC375/07-007 WC375/07-008 WC375/07-009 WC375/07-010 WC375/07-011 WC375/07-012 WC375/07-013 |
15 20 25 30 40 50 60 70 90 100 35 45 80 |
See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 See figure 1 |
3
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business