W-C-375/5C
Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
.003 |
0.08 |
.110 |
2.79 |
.280 |
7.11 |
.740 |
18.80 |
.005 |
0.13 |
.130 |
3.30 |
.290 |
7.37 |
.950 |
24.13 |
.008 |
0.20 |
.140 |
3.56 |
.375 |
9.53 |
2.187 |
55.55 |
.010 |
0.25 |
.141 |
3.58 |
.388 |
9.86 |
2.312 |
58.72 |
.013 |
0.33 |
.218 |
5.54 |
.429 |
10.90 |
2.402 |
61.01 |
.015 |
0.38 |
.230 |
5.84 |
.495 |
12.57 |
2.500 |
63.50 |
.020 |
0.51 |
.235 |
5.97 |
.565 |
14.35 |
3.000 |
76.20 |
.070 |
1.78 |
.250 |
6.35 |
.660 |
16.76 |
NOTES:
1. Dimensions are in inches.
2. Metric equivalents are given for general information only.
3. Unless otherwise specified, tolerances are ±.01 (0.25 mm) for two-place decimals and ±.005 (0.13 mm) for three-place decimals and ±1< on angles.
4. Load terminals shall be suitable for copper (CU) and aluminum (AL) wire.
FIGURE 1. Interface and physical dimensions - Continued. REQUIREMENTS:
Interface and physical dimensions: See figure 1. Trip indication: See figure 1.
Electrical:
Interrupting current rating: 10,000 amperes. Voltage rating: 120/240 V ac.
Trip current: See table I. Frequency: 60 hertz.
Calibration: At +40<C.
Enclosure for overload, endurance, and short circuit tests: Eaton # CH2L70FP, or equivalent.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
WC375/05-001 WC375/05-002 WC375/05-003 WC375/05-004 WC375/05-005 WC375/05-006 WC375/05-007 WC375/05-008 |
15 20 25 30 40 50 35 45 |
2
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.