W-C-375/30
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1.
Common trip: Both poles shall make and break simultaneously when operated manually or automatically.
Electrical:
Interrupting current rating: RMS symmetrical; 10,000 amperes. Voltage rating: 120/240 V ac.
Trip current: See table I. Frequency: 60 hertz. Calibration: At +25°C, ±3°C
Enclosure for overload, endurance, and short circuit tests: Square 0 load center Catalog No. Q0403L60NF/S used for 10 through 60 ampere breakers, and the Q03100BNF/S used for 70 through 100 ampere breakers, or equivalent.
Supersession and cross reference: See table I.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
Commercial superseded PIN CAGE 56365 |
WC375/03-001 WC375/03-002 WC375/03-003 WC375/03-004 WC375/03-005 WC375/03-006 WC375/03-007 WC375/03-008 WC375/03-009 WC375/03-010 WC375/03-011 WC375/03-012 WC375/03-013 WC375/03-014 |
15 20 25 30 35 40 45 50 60 70 80 90 100 10 |
Q0-315 Q0-320 Q0-325 Q0-330 Q0-335 Q0-340 Q0-345 Q0-350 Q0-360 Q0-370 Q0-380 Q0-390 Q0-3100 Q0-310 |