W-C-375/2C
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1.
Common trip: Both poles shall make and break simultaneously when operated manually or automatically.
Electrical:
Interrupting current rating: RMS symmetrical; 10,000 amperes. Voltage rating: 120/240 V ac.
Trip current: See table I. Frequency: 60 hertz. Calibration: At +25°C, ±3°C
Enclosure for overload, endurance, and short circuit tests: Square D load center Catalog No. Q02L30S used for 10 through 30 ampere breakers, Q024L70F/S used for 35 through 70 ampere breakers, Q02100BNF/S used for 80 through 100 ampere breakers, and the Q02125BNF/S used for the 110 and
125 ampere breakers, or equivalent.
Supersession and cross reference: See table I.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
Commercial superseded PIN CAGE 56365 |
WC375/02-001 WC375/02-002 WC375/02-003 WC375/02-004 WC375/02-005 WC375/02-006 WC375/02-007 WC375/02-008 WC375/02-009 WC375/02-010 WC375/02-011 WC375/02-012 WC375/02-013 WC375/02-014 WC375/02-015 WC375/02-016 |
15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 10 |
Q0-215 Q0-220 Q0-225 Q0-230 Q0-235 Q0-240 Q0-245 Q0-250 Q0-260 Q0-270 Q0-280 Q0-290 Q0-2100 Q0-2110 Q0-2125 Q0-210 |
3