W-C-375/12C
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1.
Common trip: All poles shall make and break simultaneously when operated manually or automatically.
Mounting: See figure 1. Electrical:
Interrupting current rating: RMS symmetrical - 10,000 amperes. Voltage rating: 240 V ac or less.
Currency rating: See table I. Frequency: 60 hertz. Calibration: At 40°C.
Enclosure for overload, endurance, and short circuit tests: General Electric Catalog No. TM12410C, or
equivalent.
Supersession data: See table II.
TABLE I. Part or Identifying Numbers (PINs) and current rating.
Government PIN |
Current rating |
WC375/12-002 WC375/12-003 WC375/12-004 WC375/12-005 WC375/12-006 WC375/12-007 WC375/12-008 WC375/12-009 WC375/12-010 WC375/12-011 WC375/12-012 WC375/12-013 WC375/12-014 |
15 20 25 30 35 40 45 50 60 70 80 90 100 |
3