W-C-375/1C
Inches |
mm |
Inches |
mm |
Inches |
mm |
Inches |
mm |
.005 |
0.13 |
.22 |
5.59 |
.50 |
12.70 |
1.38 |
35.05 |
.015 |
0.38 |
.25 |
6.35 |
.56 |
14.22 |
2.25 |
57.15 |
.033 |
0.84 |
.27 |
6.86 |
.59 |
14.99 |
2.31 |
58.67 |
.125 |
3.18 |
.30 |
7.62 |
.73 |
18.54 |
2.75 |
69.85 |
.156 |
3.96 |
.34 |
8.64 |
.94 |
23.88 |
2.92 |
74.17 |
.16 |
4.06 |
.38 |
9.65 |
1.20 |
30.48 |
3.00 |
76.20 |
NOTES:
1. Dimensions are in inches.
2. Metric equivalents are given for general information only.
3. Red luminescent trip indicator - visible only when breaker is tripped automatically. Window is dark when breaker is in ON or OFF position.
4. Line terminals shall grip a .250 (6.35 mm) wide and .125 (3.18 mm) thick buss bar.
5. Mounting clip shall grip a .250 (6.35 mm) diameter rail.
6. Unless otherwise specified, tolerances are ±0.01 (0.25 mm) for two-place decimals and ±0.005
(0.13 mm) for three-place decimals and ±1° on angles.
FIGURE 1. Interface and physical dimensions (10 through 70 amperes) - Continued.
REQUIREMENTS:
Interface and physical dimensions: See figure 1.
Trip indication: See figure 1. Electrical:
Interrupting current rating: RMS symmetrical; 10,000 amperes. Voltage rating: 120/240 V ac.
Trip current: See table I. Frequency: 60 hertz. Calibration: At +25°C, ±3°C
Enclosure for overload, endurance, and short circuit tests: Square D load center Catalog No. QO2L30S used for 10 through 30 ampere breakers, QO24L70F/S used for 35 through 70 ampere breakers, or equivalent.
Supersession and cross reference: See table I.