MS24571J
TABLE I. Electrical and mechanical characteristics.
lbs
1/ 400 Hz 115/200 volt system, tested at 120 ±5 volts 380 - 420 Hz.
Table II Detail calibration requirements.
Dash number |
Tripping time from -53.9°C to +93.3°C (time in seconds) |
||||||||
Percent rated current |
|||||||||
200 |
400 |
1000 |
3000 |
||||||
Min |
Max |
Min |
Max |
Min |
Max |
Min |
Max |
||
-2 |
-2V |
12 |
32 |
2.3 |
6.5 |
.32 |
1.1 |
.04 |
.155 |
-5 |
-5V |
14 |
36 |
2.5 |
6.5 |
.45 |
1.1 |
.06 |
.13 |
-7 |
-7V |
16 |
40 |
2.5 |
7.0 |
.34 |
1.1 |
.04 |
.12 |
-10 |
-10V |
18 |
42 |
2.7 |
7.75 |
.45 |
1.2 |
.05 |
.125 |
-15 |
-15V |
20 |
45 |
2.7 |
8.0 |
.36 |
1.2 |
.04 |
.13 |
-20 |
-20V |
20 |
48 |
2.7 |
8.0 |
.36 |
1.2 |
.04 |
.12 |
-25 |
-25V |
20 |
50 |
2.7 |
9.5 |
.36 |
1.2 |
.04 |
.12 |
-35 |
-35V |
20 |
53 |
2.7 |
8.0 |
.36 |
1.2 |
.04 |
.12 |
-50 |
-50V |
20 |
55 |
2.7 |
10.0 |
.36 |
1.4 |
--- |
--- |
3
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business