MIL-DTL-17361/16A(SH)
Adjustable instantaneous trip settings amperes/maximum time (all 3 poles) /1.
TABLE II.
LO /4
2
3
4
HI
Seconds /3
Element
60 Hz
rating /2
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
125L
650
----
780
----
900
----
1040
----
1300
----
125LM
1500
----
1770
----
2025
----
2325
----
3000
----
150L
650
----
780
----
900
----
1040
----
1300
----
150LM
1500
----
1770
----
2025
----
2325
----
3000
----
0.024
0.028
175L
650
----
780
----
900
----
1040
----
1300
----
175LM
1500
----
1770
----
2025
----
2325
----
3000
----
225L
650
----
780
----
900
----
1040
----
1300
----
225LM
1500
----
1770
----
2025
----
2325
----
3000
----
NOTES:
/1 The tolerance for each ampere setting shall not exceed ±10%.
/2 Identification marking of trip units:
Numerals indicate continuous current rating of the specific trip unit.
Letter "L" denotes that the trip units are applicable to AQB-LF226.
Letter "M" denotes calibration for applications having a high inrush current.
/3 Time shall be measured at three times the pickup current of instantaneous coil. For qualification tests only, not
for routine calibration.
/4 The LO and HI settings only are calibrated. Others are approximate.
TABLE III. Tripping characteristics long-time delay (LTD) (all 3 poles).
LTD trip element
Tripping time
% current
60-Hz AC trip element
For AC only
150
Not less than 1 hour
225
Less than 1 hour
600
Between 20 and 32 seconds