MIL-C-55629/13C
REQUIREMENTS
Dimensions and configuration: See figure 1.
Current ratings: See table I.
Voltage ratings: See table II.
Tripping-time delays: See table II.
Terminal and mounting hardware: See figure 1.
Terminals: See figure 1.
Auxiliary contact terminals: Contact capacity shall be 5 amperes to 250 volts 60/400 Hz resistive and
inductive, 1 amp resistive and .25 amp inductive at 50 V dc and 5 amp resistive and 3 amp inductive at
30 V dc.
Actuator strength: 40 pounds.
Actuator operating force: 4 pounds, maximum.
Shock:
a. MIL-STD-202, method 213, test condition I.
b. 60 G's for 21 ms.
Interrupting capacities: 5,000 amperes at 125 V dc and 240 V ac, 60 Hz and 400 Hz in accordance
with the applicable requirements of UL489. Interrupt test is not performed at 400 Hz.
High inrush. Applicable to time delay characteristics K, L, N, P, R, and S.
Vibration: Energized current shall be 80 percent of rated current and the frequency range shall be 10
to 55 Hz.
VERIFICATION:
Qualification inspection: Not applicable.
Conformance inspection: Group A tests of MIL-PRF-55629.
Part or Identifying Number (PIN): The military PIN consists of the prefix M55629/13 and two code
letters selected from tables I and II as shown in the following example.
M55629/13
A
L
One pole circuit breaker
with auxiliary contacts.________________________
Current rating code, see table I.___________________________
Voltage, frequency, and time delay
curve code, see tables I and II.___________________________________
On-off marking shall be visible with the trim or cover in place.