MIL-PRF-55629E
4.8.13 Moisture resistance (see 3.17). Circuit breakers shall be tested in accordance with method 106 of
MIL-STD-202. The following details and exceptions shall apply:
a.
Mounting - Mounted horizontally on a panel.
b.
Initial measurements - Immediately following the initial drying period, resistance or impedance shall be
measured as specified in 4.8.6.
c.
Electrical-load conditions - During the first 2 hours of step 1 and step 4, circuit breakers shall be energized at
rated current and at the applicable frequency (see 3.1).
d.
Steps 7a and 7b are not applicable.
th
Final measurements - Upon completion of the 10 cycle and while still in the humidity chamber, insulation
e.
resistance and resistance or impedance shall be measured as specified in 4.8.4 and 4.8.6, respectively.
After the 24-hour drying period, insulation resistance shall again be measured as specified in 4.8.4.
f.
Examination after test - Examine for evidence of breaking, cracking, spalling or loosening of terminals.
g.
Tests after moisture resistance test - Circuit breakers shall be subjected to the following tests:
(1) Dielectric withstanding voltage (see 4.8.3).
(2) Calibration (see 4.8.5.2) (except that tests at 400 percent, 600 percent, and 800 percent at rated current
shall not be performed).
MIL-STD-202. The following details shall apply:
a.
Mounting - Normal mounting means with at least 1 inch of free air space around each circuit breaker.
b.
Test condition - A.
c.
Examination after cycling - Circuit breakers shall be examined for evidence of mechanical damage.
4.8.15 Shock (see 3.19). Circuit breakers shall be tested in accordance with method 213 of MIL-STD-202. The
following details shall apply:
a.
Mounting method - Normal mounting means.
b.
Test condition - I (unless otherwise specified (see 3.1)).
c.
Electrical-load conditions and measurements - Of the three shocks in each direction required, two shocks
shall be performed with the circuit breaker energized at 100 percent rated current dc (see 3.1), except that
for the directions with the operating lever pivot up (table mount) and the operating lever pivot down (ceiling
mount), no voltage or current shall be applied. Each energized shock shall be monitored to determine
opening of the main and, when applicable, auxiliary contacts. The remaining shock in each direction shall
be performed with the circuit breaker contacts open and unenergized and shall be monitored to determine
closing of the main and, when applicable, of the open auxiliary contacts.
d.
Examination after shock - Circuit breakers shall be examined for evidence of mechanical and electrical
damage.
4.8.16 Trip-free calibration (see 3.20). The circuit breaker actuator shall be physically held in the closed position
18
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business